CES-I-AP-U-C04-USI-115150 Euchner 115150
 CES-I-AP-U-C04-USI-115150 Euchner 115150

We are not the manufacturer, authorised distributor or authorised representative of the Euchner brand Worldwide. The private labels and part numbers shown on this website are the property of their respective owners.

CES-I-AP-U-C04-USI-115150 115150 Euchner

Manufacturer

Euchner

Country

Germany

Name

CES-I-AP-U-C04-USI-115150

Part number

115150

Description

CES-I-AP-U-C04-USI-115150 SICHERHEITSSCHALTER UNICODE

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications CES-I-AP-U-C04-USI-115150 115150

If you are inspecting Euchner CES-I-AP-U-C04-USI-115150 115150, communicate with FAMAGA, the world's central distributor of industrial equipment. Our company has existed for more than ten years - these are years of experience, which are portrayed in the quality of products and individual attention to each client. We cherish everyone, who cooperated with us - hence, our regular clients receive the most helpful purchase forms and discounts on the manufacturing equipment market. Nowadays, there are more than 4500 such purchasers, and we constantly compose new agreements. More than 750 agreements are achieved per day, because FAMAGA supplies all over the earth . A advanced logistics series and a partnership network cheer us to conduct our elements anywhere in the earth quickly without undermining product quality.

A particular source of repute for FAMAGA is its workers, each of whom contributes to common cause. We propose into our team only experts, who already have experience in the direction of machine made streamlined equipment.

All outputs from FAMAGA are ensured - we are responsible for the aftereffect of our work. At this moment, more than 10 million units of products have been provided, and this quantity is increasing every day. We are glad that users choose FAMAGA again and again, and we are pleased to make more progressive and technologically advanced industrial equipment so as keep on top of it.

To request or make a request, get in touch with us or write a message to the online chat on our site. You can also forward a list of the needful equipment to the email of organization - we will contact you ourselves with a made commercial proposal from FAMAGA.

Features CES-I-AP-U-C04-USI-115150 115150

  • Safety switch with integrated evaluation electronics
  • No series connection
  • Short circuit monitoring
  • 2 safety outputs (semiconductor outputs)
  • Category 4/PL e according to EN ISO 13849-1
  • Three active faces
  • Connection cable PUR, 0.1 m, plug connector M12, 5-core, pin 5 not used
  • Unicode
Each actuator is unique. The switch detects only taught-in actuators. Additional actuators can be taught in. Only the last actuator taught in is detected. Category according to EN 13849-1 Due to two redundantly designed semiconductor outputs (safety outputs) with internal monitoring suitable for:
  • Category 4/PL e according to EN 13849-1
Important: To achieve the stated category in accordance with EN ISO 13849-1, both safety outputs (FO1A and FO1B) must be evaluated. LED indicator
STATEStatus LED
DIADiagnostics LED
Connector assignment
Plug connector (view of connection side) Pin Designation Function Conductor coloring of connection cable
1 UB Power supply, DC 24 V BN
2 FO1A Safety output, channel 1 WH
3 0V Ground, DC 0 V BU
4 FO1B Safety output, channel 2 BK
5 - n.c. GY
Material
Rubber support NBR 80 ±5 Shore
Housing material Plastic, PBT
Weight
Net 0,05 kg
Ambient temperature
Cable dynamic -25 ... 65 °C
Cable static -25 ... 65 °C
Degree of protection IP67
Resilience to vibration In acc. with EN IEC 60947-5-2
Mounting method Surface mounting on metal
Mounting distance
Between 2 switches or 2 actuators min.140 mm
Installation orientation Any
Tightening torque
Fixing screws max.0,8 Nm
Ready delay 0,5 s
Switching frequency max.1 Hz
Connection PUR cable 100mm with plug connector M12x1, 5-pin, pin 5 not used
Bending radius
Dynamic 10 x cable diameter
static 5 x cable diameter
Electrical connection ratings
Operating voltage DC
UB 24 V DC 15% ... 15% Regulated, residual ripple < 5%, PELV
Current consumption
No load on outputs max.35 mA
Fusing
External (operating voltage) 0,25 ... 8 A
Rated insulation voltage Ui 300 V
Rated impulse withstand voltage Uimp max.1,5 kV
EMC protection requirements In acc. with EN IEC 60947-5-3
Degree of contamination (external, according to EN 60947-1) 3
Switch-on time
Safety outputs max.300 ms
Safety class III
Risk time according to EN 60947-5-3 max.260 ms
Safety outputs FO1A / FO1B
Test pulses max.0,3 ms
Test-pulse interval min.100 ms
Type of output Semiconductor outputs, p-switching, short circuit-proof
Switching current
per safety output 1 ... 150 mA
Output voltage
LOW U(FO1A) / U(FO1B) 0 ... 1 V DC
HIGH U(FO1A) / U(FO1B) UB-1,5V ... UB V DC
Utilization category according to EN 60947-5-2
DC-13 24V 150mA
Rated conditional short-circuit current 100 A
Off-state current Ir max.0,25 mA
Discrepancy time max.10 ms
Work area
Repeat accuracy R ? 10
Other
Additional feature Rubber support included
For the approval according to UL the following applies Operation only with UL class 2 power supply, or equivalent measures
Reliability values according to EN ISO 13849-1
Monitoring of the safety guard position
Category 4
Performance Level PL e
PFHD 4.1 x 10-9
Mission time 20
In combination with Actuator CES-A-BBN-C04-115271Operating distance
Switch-on distance
Approach direction C or D (broad side) 11 mm
Approach direction A or B (front side) 15 mm
Assured operating distance Sao
Approach direction A or B (front side) min.10 mm
Approach direction C or D (broad side) min.6 mm
In combination with Actuator CES-A-BDN-06-104730Operating distance
Switch-on distance
Approach direction A or B (front side) 19 mm
Approach direction C or D (broad side) 15 mm
Assured operating distance Sao
Approach direction C or D (broad side) min.10 mm
Approach direction A or B (front side) min.14 mm
In combination with Actuator CES-A-BDN-06-104730, CES-A-BBN-C04-115271Operating distance
Assured switch-off distance Sar
In y direction max.60 mm
In x/z direction max.40 mm
Switching hysteresis min.1 mm